Tuesday, April 7, 2015

In April of 2015 we performed a chamber test of a building, during construction, following ASTM E1186 Sections 4.1.6 (using smoke) and 4.1.7 (using liquids).

The contractor applied a spray air barrier on the face of the masonry block walls and the building owner was concerned that the material wasn't applied thickly enough.    We built our testing chamber on the exterior of the wall to examine a small portion of the completed wall:

Small pin holes were visible throughout the tested assembly:

Utilizing theatrical smoke, there didn't appear to be much air movement around these small pin holes. However, when a liquid solution was applied to the tested surface, air movement became very evident.

The chamber was very helpful in demonstrating that the air barrier had not been applied thickly enough to totally eliminate all potential leakage sites.    Please visit www.tsienergysolutions.com for more information on our testing services.

Tuesday, February 17, 2015

Air Barrier Testing Video

We recently created a video that shows our entire process of testing a building for air leakage per ASTM E779 and ASTM E1827 and thermography using ASTM C1060.

Visit this link to view our new video on YouTube:  http://youtu.be/eh8MZeNiyA8

or watch it from our web site:

http://www.tsienergysolutions.com/Air_Leak_Test_ASTM_E1827.html

Monday, December 8, 2014

Last week we performed air leakage and water leakage testing at a new construction office building in Indianapolis.   The project involved chamber testing per ASTM E1186, utilizing a liquid solution and smoke to identify air leaks in a wall assembly.


A 10' x 10' air-tight chamber was constructed and sealed tightly to the exterior wall assembly.   A small fan was used to pressurize and de-pressurize the chamber while a technician used a smoke puffer and liquid solution inside the chamber to identify air leakage sites.




Using a hi-lift, we performed a water leakage test following AAMA 501.2 testing guidelines.   Horizontal and vertical seams were checked utilizing a calibrated sprayer unit.




While spraying the exterior, technicians inside the building searched for water infiltration.



For more information on water leak and air leak testing, visit http://www.tsienergysolutions.com.


Wednesday, April 23, 2014

Indianapolis ACOE Testing

In April of 2014 we performed air barrier testing on 4 military buildings in Indianapolis, IN.   The largest building had a building envelope area well over 100,000 s.f.    The buildings were amazingly tight as we are seeing a vast improvement in air barrier details and construction monitoring.
On-site ingenuity----center stabilization piece created for double doors
 
 

 
 
 
Based on the square footage of the building, 12 fans should have been required to hit the passing rate.  However this building was so tight that we only ended up using 2 of our 3-fan systems.
 
For more information on air barrier testing, please e-mail tdunn@thermo-scan.com


Tuesday, December 3, 2013

Retro-Commissioning Air Barrier Testing

As part of a retro-commissioning project at a military base in Florida, TSI performed Air Barrier Testing, Building Envelope Scans and Pressure Diagnostics for 31 existing buildings.   The goal of the project was to develop a baseline that could be used to determine priorities for energy improvements in these buildings.


Software has recently been developed that allows us to control many fans from one centralized laptop.    The software allows better control of the fans and facilitates quicker testing results.  Visit  http://www.thermo-scan.com for more information on our testing capabilities.

Monday, September 23, 2013

Air Barrier Test of

TSI just performed an air barrier test of a 37,000 sf building for the Army Corps.   This building has 2 sections:   an office area and a warehouse area.


There were a couple concerns with this building.   First, the building has a warehouse and an office section and there were concerns that the warehouse area would not be sealed tightly due to the construction type.   Second, the building has a standing seam metal roof and the client wasn't convinced they could get it sealed tightly.



Six fans were used to test this building and the building did not pass on the first run, but it was close.   With some "tweaking", the air leakage was easily reduced to bring the building into compliance.

Please visit http://www.thermo-scan.com if you have any questions regarding Air Barrier Testing.

Thursday, December 20, 2012

Air Barrier Testing Of Grocery Story (New Building)

In December 2012 we performed air barrier testing and a building envelope scan at a new grocery store in Texas. The goal of the project was to help the client identify areas where they could improve the energy efficiency of their buildings so they could implement better strategies in upcoming projects. 


Grocery stories and other similar buildings can be challenging due to unique penetrations, delivery doors,  mechanical equipment on the roof and other challenges.

Smoke was used to identify air leaks.




When trying to identify air leaks, it may be possible to use just 3 fans or 6 fans to create the necessary  pressure difference.   However, if testing to the Army Corps Of Engineer specs it would take 9-12 fans to properly pressurize or depressurize the building.

All of our inspections are performed by a Level 2 or Level 3 certified infrared thermographer and our air barrier testing technicians have years of experience testing commercial buildings.

If you need more information on air barrier testing or if you'd like to have a test performed, please visit our web site at http://thermo-scan.com/air_leak_testing.html